DODParts.com distributes related products varnishes dopes paints, aircraft parts and consumables, electrical parts, fittings and other components for the aerospace and defense industries. Submit the short price quote form for NSN 5925-01-222-4379 to receive an up to date pricing and availability quote by email.

5925-01-222-4379
Federal Supply Group
Electrical and Electronic Equipment Components
Federal Supply Classification
5925 Circuit Breakers
National Stock Number
5925-01-222-4379
Item Name Code
00136
Assigment Date
12/12/1985 (40 years ago)

1.500 inches nominal center to center distance between terminals parallel to width, 6.000 inches nominal body width, 5.940 inches nominal center to center distance between terminals parallel to length, 7.120 inches nominal body length, multipole-multiple actuator type body style

Product Characteristics

Below you’ll find the complete technical specifications and performance data for this part, including material details and compliance information.

Body Style
multipole-multiple actuator type
Body Length
7.120 inches nominal
Body Width
6.000 inches nominal
Center To Center Distance Between Terminals Parallel To Length
5.940 inches nominal
Center To Center Distance Between Terminals Parallel To Width
1.500 inches nominal
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
3.828 inches nominal
Switch Contact Arrangement
single pole, double throw
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
1.500 inches nominal
Fragility Factor
moderately rugged
Boss Height
0.220 inches nominal
Mounting Surface To Terminal End Distance
4.300 inches nominal
Pole Quantity
4
Arc Quenching Method
deion
Mounting Facility Type And Quantity
8 threaded hole
Storage Type
general purpose warehouse
Thread Quantity Per Inch
32
Maximum Continuous Load Current Rating Per Pole
130.0 amperes dc fourth location
Maximum Continuous Load Current Rating Per Pole
45.0 amperes ac first location
Maximum Continuous Load Current Rating Per Pole
45.0 amperes ac second location
Maximum Continuous Load Current Rating Per Pole
45.0 amperes ac third location
Operating Voltage Type And Rating Per Pole In Volts
130.0 dc fourth location
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac first location
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac second location
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac third location
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
10000.0 dc fourth location
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
18000.0 ac first location
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
18000.0 ac second location
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
18000.0 ac third location
Circuit Protection Type
overcurrent all locations
Trip Release Method
magnetic all locations
Trip Release Characteristic
time delay all locations
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
150.0 all locations
Reset Method
manual
Main Contact Tripping Mechanism Type
trip free
Manual Actuator Type And Quantity
4 toggle
Actuator Function
trip-reset
Actuator Position Designation
at each pole
External Actuator Linkage Arrangement
one, two, three, and four linked
Auxiliary Switch Function And Quantity
2 control
Internal Trip Release Configuration
relay trip fourth location
Internal Trip Release Configuration
series trip first location
Internal Trip Release Configuration
series trip second location
Internal Trip Release Configuration
series trip third location
Nominal Thread Size
0.190 inches
Switch Location And Position Designation
internal at each pole
Trip Delay Time In Seconds Per Rated Continuous Current
0.250 minimum at 200 pct and 1.000 maximum at 200 pct first location
Trip Delay Time In Seconds Per Rated Continuous Current
0.250 minimum at 200 pct and 1.000 maximum at 200 pct second location
Trip Delay Time In Seconds Per Rated Continuous Current
0.250 minimum at 200 pct and 1.000 maximum at 200 pct third location
Trip Delay Time In Seconds Per Rated Continuous Current
0.900 minimum at 200 pct and 1.300 maximum at 200 pct fourth location
Inclosure Protection Type For Which Designed
general purpose
Switch Terminal Type
tab, solder lug
Switch Current Rating And Type In Amps
10.0 ac and 10.0 dc
Switch Voltage Rating And Type In Volts
250.0 ac and 30.0 dc
Special Features
relay coil rated at 24.0 vdc,16.0 ohms
Frequency In Hertz
400.0 first location
Frequency In Hertz
400.0 second location
Frequency In Hertz
400.0 third location
Material
plastic case
Thread Series Designator
unc
Terminal Type And Quantity
8 threaded stud

Related Parts

This NSN group includes multiple components designed to meet specific performance and operational standards. Each listing provides detailed specs, functionality data, and replacement compatibility information:

Part Number Name
68394009-001 Circuit Breaker
GJ4-Z4-1 Circuit Breaker

FAQs

Find helpful answers about installation, operation, maintenance, compliance, and troubleshooting.

What is the FSCG of the NSN 5925-01-222-4379?
The FSCG of the NSN 5925-01-222-4379 is 5925
Does the NSN 5925-01-222-4379 have a Schedule B code assigned?
Yes, the Schedule B code is 8536200040
Does NSN 5925-01-222-4379 require demilitarization?
Items subject to the export administration regulations (ear) in parts 730-774 of title 15, code of federal regulations (cfr) (ccli or ear99) and determined by dod to present a low risk when released out of dod control. No demil, mut, or end use certificate is required. May require an export licensefrom doc.
Does NSN 5925-01-222-4379 contain precious materials?
Item does not contain precious metal.
Does NSN 5925-01-222-4379 contain hazardous materials?
Indicates there is no information in the hmirs. The nsn is in a fsc in table ii of fed std 313 and a msds may be required by the user. The requirement for a msds is dependent on a hazard determination of the supplier or the intended end use of item.
When the NSN 5925-01-222-4379 was assigned to the Federal Catalog?
It was assigned 40 years ago, on Thu, Dec 12, 1985

Professional Distribution

Certified to meet the strict requirements of defense, aerospace, and hazardous materials distribution.

  • ITAR Registered
  • DDTC Registered
  • HAZMAT Certified
  • AS9120 Quality Standards
  • 100% Quality Inspections

You May Also Like

Browse other in-demand NSN parts sourced by professionals in defense, aerospace, and manufacturing sectors. Each component meets strict standards for quality and performance.

Pricing

Submit your request below and our team will respond quickly with up-to-date pricing, delivery estimates, and stock information:

ITAR Registered

Featured Parts

Explore our most requested parts, carefully selected based on customer demand and sourcing activity. Each listing provides current specifications, availability status, and item condition:

A-78077-A
2040-01-099-6681
Propeller Seal Assy
A-7808-50
3110-00-554-3248
Annular Ball Bearing
A-7808-60
3110-00-554-3265
Annular Ball Bearing
A-7808-80
3110-00-293-9306
Annular Ball Bearing
A-7809-40
3110-00-554-3464
Annular Ball Bearing
A-7810W
4820-01-009-7918
Self Closing Valve
A-7811-20
3110-00-114-5996
Annular Ball Bearing
A-78112-01
4730-01-255-6920
Repair Kit
A-78112-01PC14
5330-01-094-6073
Preformed Packing
A-78112-01PIECE13
5331-01-094-6074
O-Ring
A-78113-01
5342-01-253-4616
Repair Kit
A-78114-01
5342-01-253-6283
Repair Kit
A-78114-01-PIECE 10
5330-01-098-7329
Wiper Ring
A-78114-01PC13
5331-01-094-4396
O-Ring
A-78114-01PC15
5331-01-093-9705
O-Ring